Mounting schemes for installing a bug damper 1. Fire bug damper: advantages, disadvantages, features of product control. To clarify the price of fire dampers, please call the indicated phones or send a request by e-mail

Flameproof explosion-proof dampers KLOP ® -1V. The valves are certified by VNIIPO EMERCOM of Russia and CA of explosion-proof and mine electrical equipment. Depending on the type of actuator, the valves are produced with an electromechanical or reversible actuator BELIMO (Switzerland) in an explosion-proof design.

The dampers can be installed in rooms from non-storage rooms to categories A or B in terms of explosion and fire hazard in accordance with Federal Law No. 123-FZ and SP 12.13130.2009, as well as in explosive zones of classes V-1, V-1a, V-1b and V-1g (according to PUE), where, according to operating conditions, the formation of explosive mixtures of gases and vapors with air is possible, belonging to categories IIA, IIB and IIC according to GOST R 51330.11-99, GOST R 51330.19-99 and to groups T1 , T2, T3, T4, T5 and T6 in accordance with GOST R 51330.5-99, as well as the formation of layers of combustible dust and explosive dust-air mixtures in accordance with GOST R IEC 61241-1-1-99. Motorized valves can be installed in explosive zones 1 and 2, according to the classification of GOST R 51330.9-99 and in zones 21 and 22 according to GOST R IEC 61241-3, in accordance with the explosion protection marking. Explosion protection markings for explosion-proof dampers with an electric drive - 1ExdIICT6 or 1ExdeIICT6 depending on the design of the input box of an explosion-proof electric drive according to GOST 12.2.020-76 and DIP A21TAT6 according to GOST R IEC 61241-1-1-99.

Fire resistance limit of valves:

Klop ® -1(60)

  • when the drive is located on the side of thermal exposure - EI 60;
  • when the drive is located on the side opposite to the thermal effect - EI 60;
  • when installing the damper on the duct section outside the enclosing
  • building structure with a rated fire resistance limit - EI 60

in the normally closed valve mode - EI 60;
in smoke valve mode - E 60.

Klop ® -1(90)

in the normally open (fire-retardant) damper mode:

  • when the drive is located on the side of thermal exposure - EI 90;
  • when the drive is located on the side opposite to the thermal effect - EI 90;
  • when installing the damper on the air duct section outside the enclosing building structure with a standardized fire resistance limit - EI 90;

in the normally closed valve mode - EI 90;
in smoke valve mode - E 90.

The valve body is made of cold rolled carbon steel and painted. By special order, stainless steel valves can be manufactured.

Fire normally open (NO) dampers in explosion-proof design are designed to block the spread of fire through air ducts, shafts and channels of ventilation and air conditioning systems of buildings and structures for various purposes. Normally closed (NC) dampers (including smoke dampers) are used as smoke dampers. The use of valves is carried out in accordance with regulatory requirements.

View climatic version U3 valves according to GOST 15150-69. The dampers can be installed indoors with ambient temperature from -30°C to +40°C in the absence of direct impact atmospheric precipitation and moisture condensation on the damper.

Environment must not contain aggressive vapors and gases in concentrations that destroy metals, paint coatings and electrical insulation.

HO (fire-retarding) dampers are produced with BELIMO electromechanical actuators (BF or BLF series) without GWS.

NC dampers (including smoke dampers) are produced with BELIMO reversible actuators (BE or BLE series).

KLOP ® -1V dampers are operable in any spatial orientation.

Characteristics and examples of valve installation schemes

Design schemes KLOP ® -1V

1 - valve body;
2 - damper;
3 - casing;
4 - drive;
5 - viewing hatch;
At A< 600 мм используется шина № 20 (А 1 =А+40 мм, B 1 =B+40 мм).

When A ≥ 600 mm, tire No. 30 is used (A 1 \u003d A + 60 mm, B 1 \u003d B + 60 mm).

L 1 \u003d 120 mm - the length of the valve body installed in the building structure.

Size range, flow section, damper projections, local resistance coefficients (LRC), the number and location of inspection hatches of the KLOP ® -1V valve are similar to the specified parameters of the KLOP ® -1 valve rectangular section.

For installation of valves in air ducts round section additional duct sections and tubular transitions can be made.

Mass of the valve KLOP ® -1V with BELIMO actuator, no more than, kg

The standard size range and design diagrams of cassettes of several dampers for installation in air ducts with cross-sectional dimensions A and B exceeding the values ​​indicated in the table are similar to the standard size range and diagrams of KLP ® -1.

The gap between the valve body and building structures is filled with cement-sand mortar or concrete. When installing the valve, it is necessary to provide access to the actuator and inspection hatches of the valve.

When installing NO (fire-retarding) dampers outside walls (ceilings), external fire protection should be applied to the edge of the casing protecting the damper drive, and in accordance with regulatory requirements, it should provide a fire resistance limit equal to the required fire resistance limit of the barrier. Valves can also be installed from the side of room A, according to the mirror (in relation to the building structure) scheme.

Designation structure of KLOP ® -1V valves when ordering and in the documentation

Order example:

KLOP-1(60)-NO-V-500x400-MV(220)

damper KLOP-1 with a fire resistance limit of 60 minutes, normally open (fire-retardant), explosion-proof, with an internal section of 500x400 mm, with a BELIMO electromechanical actuator for 220 V.

Fire-fighting normally open dampers KLOP-1 designed to block the spread of fire and combustion products. Normally closed valves KLOP-1 are used as valves for mechanical supply and exhaust smoke ventilation, the valves can also be used as smoke valves. The use of valves is carried out in accordance with regulatory requirements.

KLOP-1 dampers are not subject to installation in rooms of categories A and B due to explosion and fire hazard. In these rooms, KLOP-1 or KLOP-2 dampers are installed in an explosion-proof design.

Note: Normally open NO valves KLOP-1(60/90) can be installed both in a fire-resistant building structure (fire barrier) and outside it in a section of a fire-resistant air duct, regardless of the direction of possible thermal effects on their structures. In accordance with the requirement of clause 6.11 of SP 7.13130.2013, this allows the installation of dampers on either side of the fire barrier, regardless of the location of the fire in relation to this barrier. Compliance with the requirement of clause 6.11 is ensured by the presence of a casing that protects the drive of HO valves both when they are installed in a fire-resistant building structure, and when valves are installed in an air duct section outside this structure.

Valve design KLOP 1 NO and NC

KLOP-1 dampers are produced only in the "channel" type with two rectangular flanges). The valve actuator is installed outside the housing. Rectangular valve body is made of carbon cold-rolled steel with subsequent painting, round valve body is made of galvanized steel.

By special order, the body can be made of stainless steel. The body and damper of such valves are made of stainless steel (spanish “stainless steel”), the rest of the components and structural elements are made of carbon steel with anti-corrosion zinc coating.
The valve flaps are filled with thermal insulation.

Operating conditions KLP 1

Valves KLOP-1 workable in any spatial orientation.
When designing and installing valves in ventilation systems, it is recommended to take into account the convenience of access to the valve actuator and inspection hatches in its body.

When installing KLOP-1 dampers in air ducts large section in areas located behind the place of a sharp change in the direction of the air flow, for example, behind 90 ° bends, it is recommended to ensure the open position of the valve damper in the plane of the flow turn or use KLP-3 dampers.

Type of climatic modification of valves - U3 in accordance with GOST 15150-69. The dampers can be installed indoors with air temperatures from -30°C to +40°C, where fluctuations in temperature and air humidity are significantly less than outside the building.

The environment must be explosion-proof, not containing aggressive vapors and gases in concentrations that destroy metals, paintwork and electrical insulation.


Schemes of valve cassettes KLOP-1


Non-standard application of the KLOP 1 valve

The main feature of the fire damper KLOP-1 (60/90) is the possibility of using it for rooms with non-standard requirements. Fire damper KLOP-1 (60/90) can be made in several versions, for example:

  • For work in conditions of high humidity
    Such valves can be used on river or sea transport, stationary platforms, which is confirmed by various government certificates. The material of manufacture for such valves is high-quality stainless steel, and their Belimo electromechanical actuator is installed in a special shell with a high degree protection.
  • To work in transport
    Thanks to design features dampers KLOP-1(60/90) fire-fighting, which are intended for use in railway transport, it is possible to install them in ventilation systems and air conditioners.
  • For work in particularly demanding cleanliness rooms
    When making KLOP-1(60) for rooms with a high sterility requirement, special stainless steel is used.

You can find out more about the features of this valve by calling us. Managers of the Ventar-S company will select for you a fire damper KLOP-1 (60) for any purpose.

Valve options KLP 1

All valves KLOP-1 have a channel type of development. They are equipped with two flanges and external actuators. different types. > KLOP-1 valves with a round section can have nipple joints. Such valves are called nipple.

Normally open (NO) valves KLOP-1 are presented in several types of modifications. They can be equipped with an electromagnetic drive with a thermal lock capable of withstanding temperatures up to 72 ° C, or an electromagnetic drive without a thermal lock. Also, KLP valves can be equipped with BELIMO electromechanical actuators with thermal locking devices designed for temperatures up to 72 °C, or electromechanical actuators without such devices, and spring actuators with thermal locks that can withstand temperatures either up to 72 °С or up to 141 °С . In addition, KLOP-1 valves can be equipped with microswitches.

Normally closed (NC) and smoke dampers KLOP-1(90) and KLOP-1(60) are not equipped with thermal locks. Valves of this type, having small and medium dimensions, are equipped with an electromagnetic actuator. Large dampers KLOP-1(90) and KLOP-1(60) have BELIMO reversing actuators of the BLE or BE type or BELIMO electromechanical actuators equipped with BF or BLF return springs without TRU.

Installation of valves KLP 1

KLOP-1 valves retain their full performance when installed in any position. The design and further installation of such valves are made in accordance with calculations based on the availability of the valve for operation and accessibility to all devices that are located inside it.

KLP dampers are designed for installation indoors, where the air temperature ranges from -30 °C to +40 °C. They are installed in such a way that direct contact with natural precipitation or the formation of condensate on the valve flaps are completely excluded. If the environment surrounding the KLP valves contains aggressive vapors or gases, their concentration should not be too high. Otherwise, the aggressive environment will have a destructive effect on the metal from which the KLOP valves are made, and on the electrical insulation.

KLOP-3 dampers are designed mainly for air ducts of large cross section.

Values ​​of coefficients of local resistance


Weight of KLOP-1 valves with BELIMO actuator


Example of ordering a valve KLOP 1

Klop-1(60)-D-EM(220)-400x400-K, Where:
(60) - valve KLOP-1 with a fire resistance limit of 60 minutes,
D- smoke
EM(220)- with electromagnetic drive for 220 V,
400x400- with dimensions of internal section 400x400 mm,
TO- with terminal block

Fire-fighting normally open (fire-retarding) dampers KLP ® -1 are designed to block the spread of fire and combustion products through air ducts, shafts and channels of ventilation and air conditioning systems of buildings and structures for various purposes. Normally closed (including smoke) dampers KLOP ® -1 are used as dampers for smoke ventilation. The use of valves is carried out in accordance with regulatory requirements. KLOP ® -1 dampers are not subject to installation in rooms of categories A and B in terms of explosion and fire hazard.

Fire resistance limit of valves:

KLOP ® -1 (60) - in the mode of normally open (fire-retardant) and normally closed - EI 60;
in smoke mode - EI 60, E 60.
KLOP ® -1 (90) - in the mode of normally open (fire-retardant) and normally closed - EI 90;
in smoke mode - EI 90, E 90.

KLOP ® -1 dampers are produced only in “channel” type with two flanges (rectangular and round valves) or with nipple connection (round valves). The valve actuator is installed outside the housing. Rectangular valve body is made of cold-rolled carbon steel with subsequent painting, round valve body is made of galvanized steel.

Normally open (NO) valves KLOP ® -1 are manufactured in various modifications depending on the type of drive:

  • with electromagnetic drive in combination with a 72°C thermal lock (or without it);
  • round valves with electromagnetic drive are manufactured without thermal lock;
  • with BELIMO electromechanical actuators (BF or BLF) in combination with (or without) a 72°C thermal cut-out device;
  • with spring drive and thermal lock at 72°C or 141°C, with or without microswitches.

Normally closed (NC), including smoke dampers KLP ® -1 (60) large sizes). On valves manufactured for foreign countries, electromechanical actuators BELIMO with a return spring type BF or BLF without TRU can also be installed.

KLOP ® -1 dampers are operable in any spatial orientation.

When designing and installing valves in ventilation systems, the convenience of access to the valve actuator and inspection hatches in its body should be taken into account. In air ducts of large cross section, crossing the enclosing structures of ventilation chambers with high-capacity fans installed in them, it is recommended to install KLOP ® -3 dampers.

Type of climatic modification of valves - U3 in accordance with GOST 15150-69. The dampers can be installed indoors with an ambient temperature of -30°C to +40°C in the absence of direct exposure to atmospheric precipitation and moisture condensation on the damper. The environment must be explosion-proof, not containing aggressive vapors and gases in concentrations that destroy metals, paintwork and electrical insulation.

Design schemes KLOP ® -1

1 - valve body; 2 - damper; 3 - protective cover; 4 - drive; 5 - thermal lock; 6 - inspection hatch; 7 - key; 8 - damper retainer ring; 9 - TRU; 10 - terminal block; 11 - damper position indicator; 12 - key socket for manual cocking of the drive spring; 13 - lever for manual actuation of the damper drive

L1=120 mm is the length of the valve body from the flange to the edge of the protective casing.
In valves with dimensions, A< 600 мм используется шина № 20 (А1=А+40 мм, B1=B+40 мм).
Valves with dimensions A ≥600 mm use busbar No. 30 (A1=A+60 mm, B1=B+60 mm).

At, A<600 мм один смотровой люк располагается в центре боковой поверхности клапана слева (вид со стороны привода),
and when, A≥600 mm - one hatch in the upper part of the side surface on the right (see Fig.) and the second hatch in the lower part of the opposite surface on the right.

On valves with electromechanical actuator BELIMO at V< 400 мм ТРУ устанавливается на крышке люка клапана, а при В ≥400 мм — на корпусе рядом с приводом.

The area of ​​the passage section of the KLOP ® -1 valves of rectangular section is determined by the formula:

Fcl \u003d (A - 36) (B - 63) / 10 6, m 2

where, A, B are the internal dimensions of the cross section of the damper (air duct), mm, (A≥B).

Values ​​of damper projections for the valve body of rectangular section

B, mm 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
X, mm 0 0 22 47 72 97 122 147 172 197 222 247 272 297 322 347 372 397
X1, mm 0 0 0 0 0 0 0 0 12 37 62 87 112 137 162 187 212 237

Х — damper projection at the valve inlet, mm; X1 - flap projection at the outlet of the valve, mm

Installation schemes for KLOP ® -1 valves are presented on pages 68, 69.

To compensate for the length of the damper projection (for example, when installing a decorative grille on a flange or when installing a damper in a building structure with a thickness of more than L1, additional duct sections of the appropriate length can be made.

Cassette schemes

Version 1 (welded)


9 - self-tapping screw.

Fk \u003d (Ak - 126) (Bk - 36) / 10 6, m 2


Execution 2.1 (Вк≤300 mm, welded)

1 - body; 2 - damper; 3 - protective cover; 4 - drive; 5 - inspection hatch; 6 - TRU (for NO valves); 7 - junction box with terminal block; 8 - bar;
9 - self-tapping screw.

Fk \u003d (Ak - 72) (Bk - 63) / 10 6, m 2

Ak, Bk - dimensions of the internal section of the cassette (air duct), mm
Fк - area of ​​the passage section of the cassette, m 2

Execution 2.2 (Вк > 300 mm, on slats)

1 - body; 2 - damper; 3 - protective cover; 4 - drive; 5 - inspection hatch; 6 - TRU (for NO valves); 7 - junction box with terminal block; 8 - bar;
9 - self-tapping screw.

Fk \u003d (Ak - 132) (Bk - 63) / 10 6, m 2

Ak, Bk - dimensions of the internal section of the cassette (air duct), mm
Fк - area of ​​the passage section of the cassette, m 2

Round valves

Valves are made of galvanized steel.

Design schemes KLOP ® -1 round section

With BELIMO drive With electromagnetic drive With spring drive and TK

for flanged valve
L=350mm, Lo=93mm, L1=120mm;
For nipple valve
L=450mm, Lo=143mm, L1=175mm
L1 - valve body length up to
edges of the protective cover, mm
1 - valve body
2 - damper
3 - protective cover
4 - drive
5 - inspection hatch
6 - key
7 - TRU
8 - damper retainer ring
9 - thermal lock
10 - damper position indicator
11 - key socket for manual
cocking the drive spring
12 - manual actuation lever
damper actuator

Values ​​for damper projections outside the valve body

D, mm 160 180 200 225 250 280 315 355 400 450 500 560 630 710 800
with flange connection
X, mm 0 0 7 19 32 47 64 85 107 132 157 187 222 262 307
X1, mm 0 0 0 0 0 0 0 0 0 0 0 16 51 91 136
with nipple connection
X, mm 0 0 0 0 0 0 14 35 57 82 107 137 172 212 257
X1, mm 0 0 0 0 0 0 0 0 0 0 0 0 0 41 86

By special order, valves with a diameter of 900 and 1000 mm with a BELIMO actuator can be manufactured.

Standard size range of KLOP ® -1 dampers of circular cross section and junctions, values ​​of local resistance coefficients of dampers zB and dampers with two junctions zB * and area of ​​the flow section of dampers Fcl depending on the diameter of the internal section of the air duct D.

Flanged and nipple valves with a diameter of 160 and 180 mm are manufactured only with an electromagnetic actuator or a BELIMO actuator.

For installation in air ducts with a diameter of 100 and 125 mm, flanged dampers with a diameter of 160 or 200 mm are manufactured with tubular or plate transitions.

For installation in air ducts with a diameter of 140 mm, flanged dampers with a diameter of 160 mm with tubular transitions or flanged dampers with a diameter of 200 mm with plate transitions are manufactured.

Weight of KLOP ® -1 valves, kg

D, mm 160 180 200 225 250 280 315 355 400 450 500 560 630 710 800
flanged
TK - - 5,0 5,6 6,2 6,8 7,7 10,2 11,8 13,5 15,7 18,3 21,5 26,0 29,4
BELIMO 6,1 6,8 7,6 8,2 8,8 9,5 10,5 13,0 14,5 16,2 18,4 21,0 24,2 28,7 32,9
EM 6,3 7,0 7,8 8,3 9,0 9,7 10,6 13,2 14,7 16,4 18,6 21,2 24,5 28,9 33,1
nipple
TK 3,9 4,1 4,3 4,5 5,0 5,4 6,2 8,5 9,8 11,3 13,3 15,6 18,5 25,3 29,5
BELIMO 4,8 5,0 5,2 5,6 6,1 6,6 7,5 9,8 11,1 12,5 14,6 16,8 21,2 28,8 33,1
EM 6,1 6,4 6,7 7,1 7,7 8,2 9,0 11,4 12,6 14,1 16,1 18,4 21,4 28,9 33,3

Fire-fighting normally open (fire-retarding) dampers KLOP®-1 are designed to block the spread of fire and combustion products through air ducts, shafts and channels of ventilation and air conditioning systems of buildings and structures for various purposes. Normally closed KLOP®-1 dampers are used as dampers for mechanical supply and exhaust smoke ventilation, the dampers can also be used as smoke dampers. The use of valves is carried out in accordance with regulatory requirements. KLOP®-1 dampers are not subject to installation in rooms of categories A and B due to explosion and fire hazard. In these rooms, KLOP®-1 or KLOP®-2 dampers in an explosion-proof design are installed.

Fire resistance limit of valves KLOP®-1(60/90)

In normally open (fire-retardant) damper mode:

  • when the drive is located on the side of thermal exposure - EI 60/90;
  • when the drive is located on the side opposite to the thermal effect - EI 60/90;
  • when installing the damper on the duct section outside the enclosing
  • building structure with a rated fire resistance limit - EI 60/90;

- in the normally closed valve mode - EI 60/90;

– in smoke valve mode - E 60/90.

When deciding on the use of fire dampers, it is advisable to take into account the advantages of the new generation of KLOP®-2 dampers with improved characteristics (see the KLOP®-2 section). In accordance with the entry in the NO certificates, dampers KLP®-1 (60/90) can be installed both in a fire-resistant building structure (fire barrier) and outside it in a section of a fire-resistant air duct, regardless of the direction of possible thermal effects on their structures. In accordance with the requirement of clause 6.11 of SP 7.13130.2013, this allows the dampers to be installed on either side of the fire barrier, regardless of the location of the fire in relation to this barrier. Compliance with the requirement of clause 6.11 is ensured by the presence of a casing that protects the drive of HO valves both when they are installed in a fire-resistant building structure, and when valves are installed in an air duct section outside this structure.

Normally open (NO) valves KLOP®-1 are manufactured in various modifications depending on the type of drive:

– with an electromagnetic drive in combination with a thermal lock at 72°C (by special order at 93 or 141°C);

– with BELIMO electromechanical actuators type BFL, BFN or BF (for larger valves) in combination with a thermal disconnector at 72°C (on special order at 93 or 141°C);

Normally closed (NC) KLP®-1 dampers are produced with an electromagnetic actuator without a thermal lock or BELIMO reversible actuators of the BLE, BEN, BEE or BE type (for large valves). Drive characteristics and electrical circuits their connections are shown on pages 78-83.

KLOP®-1 dampers are produced of rectangular section only of the "channel" type with two flanges. The valve actuator is installed outside the housing. The valve body is made of cold rolled carbon steel and painted. By special order, the body can be made of stainless steel. The body and damper of such dampers are made of stainless steel (spanish "stainless steel"), other components and structural elements are made of carbon steel with anticorrosive zinc coating. The valve flaps are filled with thermal insulation.

KLOP®-1 dampers are operable in any spatial orientation. When designing and installing valves in ventilation systems, it is recommended to take into account the convenience of access to the valve actuator and inspection hatches in its body. When installing KLOP®-1 dampers in large-section air ducts in areas located behind the place of a sharp change in the direction of the air flow, for example, behind 90° bends, it is recommended to ensure the open position of the damper damper in the plane of flow turn or to use KLOP®-3 dampers. Type of climatic modification of valves - U3 in accordance with GOST 15150-69. The dampers can be installed indoors with air temperatures from -30°C to +40°C, where fluctuations in temperature and air humidity are significantly less than outside the building. The environment must be explosion-proof, not containing aggressive vapors and gases in concentrations that destroy metals, paintwork and electrical insulation.

Fire dampers KLOP 1

Fire dampers normally open (NO), normally closed (NC) and smoke bugs 1 ( KLOP -1) have been certified by VNIIPO of the Ministry of Emergency Situations of the Russian Federation and the Republican Certification Center of the Ministry of Emergency Situations of the Republic of Belarus.

Purpose

Installation ok open valves KLP 1 helps prevent the spread of fire and combustion products propagating through the channels of air conditioning and ventilation systems, channels of mines and air ducts installed in buildings and structures for various purposes. NO and smoke dampers are recommended for installation in smoke ventilation systems.

Installation, operation and maintenance of KLOP-1 valves are carried out in accordance with the requirements of technical documentation and special specifications. valves KLOP -1 are not installed in explosion-hazardous rooms of categories A and B. In such cases, it is recommended to install valves KLOP -1 In explosion-proof or explosion-proof execution.

Fire resistance limits of valves KLOP-1:

BUG -1 (60) - in NO and NC modes - E l 60;

In smoke valve mode - E l 60, E 60.

bug -1 (90) - in NO and NC modes - E l 90;
- in smoke valve mode - E
l 90, E 90.

Valves KLOP-1 are produced exclusively in channel version with an external drive and two flanges. Normally open valves (NO) can be made in various modifications and equipped with actuators various types, including:

KLOP valves -1 with an electromagnetic drive with a possible configuration with a thermal lock (TK) on 72°C;

KLOP valves -1 with an electromagnetic drive of circular cross section (without TK);

KLOP valves -1 with BELIMO electromechanical drive (BLF or BF) 72°C;

KLOP valves -1 with spring type drive and TK on72°С or ТЗ at 141°С with a possible complete set of microswitches.

Liked the article? Share with friends: